Electronics Guide

Transmission and Distribution Lines

Most of the electricity a customer uses travels over two kinds of line. Transmission lines carry bulk power at hundreds of kilovolts from generating stations and between regions; distribution lines carry it the last few kilometers, at a few kilovolts to a few tens of kilovolts, to the transformers that serve homes and businesses. Each has series resistance and inductance and shunt capacitance, and those parameters decide how much power it can carry, how far its voltage sags or rises, and how much energy it turns into heat.

This article treats alternating-current lines in sinusoidal steady state: line parameters and models, surge impedance loading, the Ferranti effect, voltage drop, losses, compensation, distribution feeders, and the charging and thermal limits of cables. Direct-current lines belong to HVDC transmission systems.

The distributed-parameter equations used here are the telegrapher's equations that also describe a circuit-board trace, but the regime is the opposite one. A 60 Hz wave on an overhead line has a wavelength of nearly 5,000 km, so even a very long power line spans only a fraction of a wavelength, and its behavior turns on voltage magnitude, reactive power, and heat rather than on reflections. Transmission line fundamentals covers the high-frequency case. Throughout, the line is assumed to be balanced, so one phase and the neutral represent the whole three-phase circuit, as described in three-phase circuits and power.

Lines in the Power System

Power systems are layered by voltage. Step-up transformers at generating stations raise voltage for transmission, where North American practice uses levels such as 115, 138, 230, 345, 500, and 765 kV. Subtransmission lines carry power onward to distribution substations, which step it down to primary voltage for the feeders that supply distribution transformers and, through them, customers. Utilities draw the boundaries between these layers differently.

High voltage pays off in two ways. For a given power, line current is inversely proportional to voltage, so resistive loss falls with the square of voltage, and the power a line can carry before voltage drop or stability limits it rises with the square of voltage.

Overhead Lines

An overhead line hangs bare conductors from insulators on towers or poles and uses the air as insulation. Most conductors are stranded aluminum, which conducts about 61 percent as well as copper but is so much lighter that a conductor of equal resistance weighs about half as much. The workhorse design, aluminum conductor steel reinforced (ACSR), wraps aluminum strands around a steel core that carries much of the tension. All-aluminum and aluminum-alloy conductors serve many distribution lines, and high-temperature designs such as aluminum conductor steel supported (ACSS) and composite-core conductors carry more current with less sag. Shield wires above the phases intercept lightning, and many carry optical fibers.

Two physical limits shape the design. A conductor sags as it heats and must keep a safe clearance above the ground. And the electric field at its surface must stay below the level at which air ionizes, roughly 3 MV/m under standard conditions; near that gradient a conductor goes into corona, which wastes energy, produces audible noise and radio interference, and degrades hardware. Lines at 345 kV and above therefore usually carry bundles of two or more subconductors per phase, which spread the charge over a larger effective surface.

Underground Cables

A cable replaces the air with solid insulation a few centimeters thick. A high-voltage cable has a stranded copper or aluminum conductor; a semiconducting conductor screen that smooths the field at the conductor surface; the main insulation; a semiconducting insulation screen; a metallic sheath or wire screen that carries charging and fault current and holds the outer surface at ground potential; and a protective jacket. Extruded cross-linked polyethylene (XLPE) is the usual insulation for new cable, ethylene propylene rubber (EPR) is common at distribution voltages, and older networks still contain paper-insulated lead-covered cable and fluid-filled cable in steel pipes.

Cables cost considerably more than overhead lines of similar rating, but they are the practical choice beneath dense cities, across water, and where an overhead route cannot win approval. Electrically, a cable is the opposite of an overhead line: its conductor sits a few centimeters from a grounded screen, so its inductance is low and its capacitance high, which produces the charging-current limit discussed below.

Series Resistance

The direct-current resistance of a conductor is R = ρl/A, for resistivity ρ, length l, and cross-sectional area A. Three corrections turn that value into the one used in line studies. First, stranding: each strand follows a helix, so it is slightly longer than the conductor, which raises resistance by a percent or two. Second, temperature: resistance rises with temperature according to

R2 = R1 (T + t2) / (T + t1)

where t1 and t2 are conductor temperatures in degrees Celsius and T is the temperature at which the extrapolated resistance would reach zero. For hard-drawn aluminum, T is about 228 °C, so resistance at 75 °C is about 22 percent higher than at 20 °C. Third, skin effect: alternating current crowds toward the surface of a conductor, and in the large conductors of transmission lines the resistance at 50 or 60 Hz exceeds the direct-current value by a few percent.

Manufacturers publish AC resistance at power frequency for two or more temperatures, and a line study should use the value at the operating temperature it assumes. Shunt conductance, which represents leakage across insulators and corona loss, is small enough to neglect in most steady-state studies.

Series Inductance: GMR, GMD, and Transposition

The Inductance of a Round Conductor

Current in a conductor produces magnetic flux inside and outside it. For a long, straight, nonmagnetic round conductor of radius r whose current I is spread uniformly over its cross section, the internal flux linkage is μ0I/(8π) per meter, and the external flux linkage out to a distance D is (μ0I/2π) ln(D/r). With μ0/2π = 2 × 10−7 H/m, the total per meter is

λ = 2 × 10−7 I (1/4 + ln(D/r)) = 2 × 10−7 I ln(D/r′) Wb/m, where r′ = e−1/4 r ≈ 0.7788 r

The fictitious radius r′ is the conductor's geometric mean radius (GMR): a thin-walled tube of radius r′, which has no internal flux, would have the same inductance. The uniform current density assumed here is a reasonable approximation at power frequency.

Three-Phase Lines and Transposition

For a balanced three-phase line whose conductors sit at the corners of an equilateral triangle of side D, the flux from the other two phases combines so that each phase has an inductance of 2 × 10−7 ln(D/r′) H/m. Real lines rarely have equal spacing. The middle phase of a flat, horizontal line is closer to both outer phases than they are to each other, so each phase has a different inductance, and balanced currents produce unbalanced voltage drops.

Transposition removes the difference on average. The line is divided into three sections of equal length, and the phases exchange positions at transposition structures so that every phase occupies every position for one-third of the length. The per-phase inductance of the transposed line is then

L = 2 × 10−7 ln(GMD/GMR) H/m, where GMD = (Dab Dbc Dca)1/3

and the geometric mean distance (GMD) is the geometric mean of the three phase spacings. At 60 Hz, the per-phase reactance is X = 0.0754 ln(GMD/GMR) Ω/km; at 50 Hz, the coefficient is 0.0628. Spacing enters through a logarithm, so doubling every distance adds only 0.0523 Ω/km at 60 Hz. Many lines are transposed only partially or not at all; detailed studies then use the full matrix of self and mutual phase impedances, and the remaining asymmetry appears as negative-sequence and zero-sequence voltage that grows with load.

Stranded Conductors and Bundles

A stranded conductor behaves as a group of parallel subconductors. Its GMR is the geometric mean of all distances between strands, with each strand's own r′ as its distance to itself. Seven identical strands give 0.726 times the overall radius, and ideal concentric layers approach the solid value of 0.7788: about 0.758 for 19 strands and 0.768 for 37. Multilayer ACSR can exceed the solid value, because its steel core carries little current, and current confined to an outer ring has a larger GMR. In practice, engineers take GMR from the manufacturer's table.

A bundle is treated the same way. For subconductors of GMR Ds spaced a distance d apart, the bundle GMR is

(Ds d)1/2 for two subconductors, (Ds d2)1/3 for three in a triangle, and 1.09 (Ds d3)1/4 for four in a square

A bundle's GMR is several times that of a single subconductor, so bundling lowers series inductance substantially. For the same geometric reason, it raises capacitance and lowers the surface gradient that causes corona.

These expressions give the positive-sequence impedance that governs balanced operation. Current returning through the earth and shield wires, as ground-fault current does, sees a substantially larger impedance, calculated with the ground-return corrections that John R. Carson published in 1926; that zero-sequence impedance matters mainly in fault calculations with symmetrical components.

Shunt Capacitance

A charged conductor produces a radial electric field. For a long line charge q in coulombs per meter, the potential difference between points at distances D1 and D2 from it is (q/2πε0) ln(D2/D1). Applying that result to all three phases of a transposed line gives the capacitance from each phase to neutral:

Cn = 2πε0 / ln(GMD/r) F/m ≈ 55.6 / ln(GMD/r) nF/km

The formula uses the physical outside radius r, not the GMR, because charge resides on the conductor's surface and there is no internal term like the one that produced r′. For a bundle, replace r with the capacitive radius from the bundle expressions, using r in place of Ds. The earth's effect, captured by the method of images, is small when the conductors are high above the ground compared with their spacing.

Charging Current and Reactive Power

Shunt capacitance draws charging current whether or not the line carries load. Per unit length, each phase draws Ic = ωCnVph, and the three phases generate reactive power Qc = ωCnVLL2, where Vph and VLL are the phase-to-neutral and line-to-line voltages. The series inductance absorbs 3I2ωL per unit length, which depends on load. Whichever is larger decides whether the line raises or lowers the voltage around it.

The product of the inductance and capacitance formulas is nearly the same for every overhead line: LCn = μ0ε0 ln(GMD/GMR) / ln(GMD/r), only slightly more than 1/c2. Waves on an overhead line therefore travel at nearly the speed of light.

Worked Example: Parameters of a 345 kV Line

A transposed 345 kV line has its phases in a flat row, 8 m apart, so Dab = Dbc = 8 m and Dca = 16 m. Each phase is a bundle of two subconductors spaced 0.45 m apart. Each ACSR subconductor has an outside diameter of 28.1 mm and a GMR of 11.4 mm; these are illustrative values.

  1. Geometric mean distance: GMD = (8 × 8 × 16)1/3 = 10.08 m.
  2. Bundle radii: the GMR for inductance is (0.0114 × 0.45)1/2 = 0.0716 m, and the capacitive radius is (0.01405 × 0.45)1/2 = 0.0795 m.
  3. Inductance: L = 2 × 10−7 ln(10.08/0.0716) H/m = 0.989 mH/km, so X = 0.373 Ω/km at 60 Hz.
  4. Capacitance: Cn = 55.6/ln(10.08/0.0795) = 11.49 nF/km, so the shunt susceptance is ωCn = 4.33 µS/km.
  5. Charging: at 345 kV, the line generates ωCnVLL2 = 0.516 Mvar/km, or about 155 Mvar over 300 km.

Used singly, one per phase, the same conductors would give 0.512 Ω/km and 8.46 nF/km, so bundling cuts the series reactance by 27 percent and raises the capacitance by 36 percent. The propagation velocity, 1/√(LCn), is 0.989 times the speed of light.

Line Models: Short, Medium, and Long

A line study needs the relationship between the sending end, S, and the receiving end, R, which for a linear, passive, bilateral network takes the transmission-parameter, or ABCD, form:

VS = A VR + B IR

IS = C VR + D IR

V is phase-to-neutral voltage and I is line current, both phasors in sinusoidal steady state, with IR flowing toward the load. A and D are dimensionless, B is an impedance, and C is an admittance, not a capacitance. A line is reciprocal, so AD − BC = 1, and symmetric, so A = D. Two-port networks develops the parameters in general; power engineers use them to cascade lines, transformers, and compensation by multiplying matrices.

The models below use the series impedance per unit length, z = r + jωL, where r now denotes resistance per unit length rather than conductor radius, and the shunt admittance per unit length, y = g + jωCn, which is nearly jωCn. For a line of length l, the totals are Z = zl and Y = yl.

Short Line

When the shunt admittance is negligible, the line is a series impedance Z, so A = D = 1, B = Z, and C = 0. The model ignores charging current entirely.

Medium Line: The Nominal π Circuit

The nominal π circuit places half the total shunt admittance at each end of the series impedance. The current through Z is IR + VRY/2, so VS = VR + Z(IR + VRY/2). The sending-end current adds the charging current of the sending-end admittance, VSY/2. Collecting terms gives

A = D = 1 + ZY/2, B = Z, C = Y(1 + ZY/4)

Long Line: Distributed Parameters

A long line must be treated as distributed. Measure distance x from the receiving end. Over a length dx, the voltage rises by the series drop zI dx and the current rises by the shunt current yV dx:

dV/dx = zI, dI/dx = yV

Differentiating again gives d2V/dx2 = zyV, whose solutions are waves traveling in both directions with propagation constant γ = √(zy) = α + jβ. The ratio of voltage to current in either wave is the characteristic impedance, Zc = √(z/y). Power engineers usually write Zc, keeping Z0 for zero-sequence impedance. Applying V = VR and I = IR at x = 0 and evaluating the solution at x = l gives

A = D = cosh γl, B = Zc sinh γl, C = (sinh γl)/Zc

The exact line can also be drawn as an equivalent π circuit whose elements are the nominal values multiplied by correction factors:

Z′ = Z (sinh γl)/(γl), Y′/2 = (Y/2) tanh(γl/2)/(γl/2)

Both factors approach 1 as γl approaches zero, which is why the nominal π circuit converges on the exact result as a line gets shorter.

The Lossless Line

Neglecting resistance and conductance makes γ = jβ purely imaginary and Zc real, with L and Cn per unit length:

β = ω√(LCn), Zc = √(L/Cn), A = D = cos βl, B = jZc sin βl, C = j(sin βl)/Zc

High-voltage lines have series reactance many times their resistance, so the lossless form describes them well. Substituting the overhead-line formulas gives a quick estimate: Zc ≈ 60 √(ln(GMD/GMR) × ln(GMD/r)) Ω.

Choosing a Model

Textbooks sort lines into short, medium, and long classes by length, with differing boundaries, but the real criterion is electrical length, βl. For the 345 kV example line carrying 400 MW at unity power factor, the short-line model overstates the sending-end voltage by 0.5 percent at 80 km and 4.7 percent at 250 km, and even at 80 km it misstates the sending-end reactive power by about 42 Mvar because it ignores charging. The nominal π model stays within 0.25 percent out to 250 km and is off by about 1.1 percent at 400 km. At 50 Hz, β is five-sixths of its 60 Hz value, so each model holds its accuracy over a line about one-fifth longer.

Worked Example: A 300 km 345 kV Line

The line from the parameter example is 300 km long, with an illustrative bundle resistance of 0.040 Ω/km, and delivers 400 MW at unity power factor to a receiving bus held at 345 kV.

  1. Constants per kilometer, carried unrounded from the parameter example: z = 0.040 + j0.373 Ω/km and y = j4.33 µS/km.
  2. Propagation constant and characteristic impedance: γ = √(zy) = (0.0681 + j1.2728) × 10−3 per km, and Zc = √(z/y) = 294.3 e−j3.06° Ω. Over 300 km, γl = 0.0204 + j0.3818, an electrical length of 21.9°.
  3. ABCD constants: A = D = cosh γl = 0.9282 + j0.0076; B = Zc sinh γl = 11.42 + j109.23 Ω; and C = (sinh γl)/Zc = (−0.0033 + j1.2681) × 10−3 S.
  4. Receiving end: VR = 345/√3 = 199.19 kV phase to neutral, and IR = 400 MW/(3 × 199.19 kV) = 669.4 A, in phase with VR.
  5. Sending end: VS = AVR + BIR = 206.5 ej21.2° kV phase to neutral, which is 357.6 kV line to line, or 1.037 times nominal. IS = CVR + DIR = 672.0 ej22.5° A.
  6. Power and loss: the sending end supplies 416.2 MW, so the line loses 16.2 MW and delivers 96.1 percent of the power sent. Reactive power of 9.9 Mvar flows from the line back into the sending system, because the load is just below the line's surge impedance loading.
  7. Regulation: removing the load with |VS| held fixed raises the receiving voltage to |VS|/|A| = 385.3 kV line to line, so the voltage regulation is (385.3 − 345)/345 = 11.7 percent.
Sending-End Results for the 300 km Line by Model
Model |VS|, line to line (kV) Sending-end Q (Mvar) Loss (MW) Regulation (%)
Long (exact)357.6−9.916.211.7
Nominal π359.1−5.116.712.3
Short381.6+150.416.110.6

The nominal π circuit overstates the exact sending-end voltage by 0.4 percent. The short-line model errs by 6.7 percent and, worse, says that the sending system must supply 150 Mvar, when the line's own charging more than covers its reactive losses at this load.

Surge Impedance Loading and Line Loadability

Terminate a lossless line in a resistance equal to Zc, and the reflected wave vanishes. With IR = VR/Zc, the distributed solution becomes V(x) = VR ex: the voltage has the same magnitude everywhere, and only its phase advances toward the sending end. At that load, the reactive power the capacitance generates per phase and per unit length, ωCnVph2, exactly equals the reactive power the inductance absorbs, ωLI2, because Vph/I = √(L/Cn). The three-phase power delivered is the surge impedance loading (SIL), or natural load:

SIL = VLL2 / Zc

SIL is in megawatts when VLL is in kilovolts and Zc is in ohms, and it depends on voltage and conductor geometry but not on length. Below SIL, a line generates net reactive power and raises the voltage along its length; above SIL, it absorbs reactive power and depresses the voltage. The example line, with its resistance neglected, has Zc = 293.5 Ω and an SIL of 406 MW at 345 kV.

Because SIL grows with the square of voltage and falls as surge impedance rises, it increases with voltage class and with bundling. Single-conductor overhead lines have surge impedances near 400 Ω, and bundled extra-high-voltage lines fall to roughly 240 to 280 Ω.

Published Surge Impedance Loading Values
Nominal voltage Phase conductors SIL (MW) Implied Zc (Ω) Source
138 kVNot stated48397St. Clair, 1953
230 kVNot stated132401St. Clair, 1953
345 kVBundle of two 1,590 kcmil ACSRAbout 430About 280MISO, 2023
500 kVBundle of three 954 kcmil ACSR936267MISO, 2023
765 kVBundle of six 795 kcmil ACSR2,435240MISO, 2023

The 1953 values are from H. P. St. Clair's table as reprinted by Dunlop, Gutman, and Marchenko in 1979. The others are from planning materials that the Midcontinent Independent System Operator (MISO) presented to its Planning Advisory Committee on March 8, 2023, computed from typical conductor configurations and spacings. The implied surge impedance is VLL2/SIL.

The St. Clair Curve

SIL is a natural yardstick for practical loading. In a paper presented at an AIEE meeting in Vancouver in September 1953, H. P. St. Clair of American Gas and Electric, later American Electric Power, gave curves of loadability, in multiples of SIL, against line length, drawn from experience rather than analysis. His benchmarks were 3.0 SIL for a 50-mile line, where thermal limits govern, and 1.0 SIL for a 300-mile line, a length at which lines were known to run with little or no reactive power supplied from either end.

In 1979, R. D. Dunlop, R. Gutman, and P. P. Marchenko of the American Electric Power Service Corporation derived the curve analytically and extended it to extra-high and ultra-high voltages. Their criteria were a voltage drop across the line of no more than 5 percent and a steady-state stability margin of 30 percent, that is, operation at no more than 70 percent of the maximum transferable power. Their curves came out nearly identical to St. Clair's, although the strength of the terminal systems mattered more as the voltage class rose.

MISO applies the curve as a safe loading limit, the lesser of the load that produces a 5 percent voltage drop across the line and the load that produces an angular displacement of 44.5 degrees; voltage drop governs shorter lines, and angle governs longer ones. Its multipliers fall from 3.00 at 50 miles to 2.05 at 100, 1.60 at 150, 1.30 at 200, and 1.00 at 300. By that measure, the 300 km (186-mile) example line could carry roughly 1.4 times its SIL, about 560 MW.

Power Transfer Over a Lossless Line

The lossless constants also give the power a line transfers between two buses whose voltage magnitudes are held fixed:

P = VSVR sin δ / (Zc sin βl)

Here VS and VR are line-to-line voltage magnitudes, δ is the angle by which VS leads VR, and P is three-phase power; for a short line, Zc sin βl approaches the series reactance X. The dynamics near the theoretical maximum at δ = 90° belong to power system stability. For the example line with both ends at 345 kV, an angle of 30° transfers 545 MW, or 1.34 SIL.

The Ferranti Effect

A long line that is open or lightly loaded at its receiving end delivers a voltage higher than the one applied at its sending end. The effect is named for the British engineer Sebastian Ziani de Ferranti. With the receiving end open, IR = 0 and VS = AVR, so

VR/VS = 1/cosh γl, which for a lossless line is 1/cos βl

For small βl, cos βl ≈ 1 − (βl)2/2, so the rise is about (βl)2/2. It grows with the square of line length and with the square of frequency. The nominal π circuit predicts the same approximation, because 1 + ZY/2 = 1 − ω2LCnl2/2 for a lossless line.

The cause is charging current flowing through series inductance. Charging current leads the voltage by 90°, so the voltage it develops across the series reactance lies in phase with the line voltage and raises it toward the open end, and the charging current of the far portions of the line flows through all of the inductance nearer the source. On the open 300 km example line, the midpoint voltage is 1.058 times the sending voltage, and the open-end voltage is 1.077 times.

Ferranti Rise on an Open-Ended Lossless Line at 60 Hz (propagation velocity 0.989c)
Length (km) βl (degrees) VR/VS Rise (%)
1007.31.0080.8
20014.61.0333.3
30021.81.0777.7
40029.11.14514.5
50036.41.24324.3

In service, charging current also flows through the source impedance behind the sending bus, so an open line fed from a weak system can exceed the values in the table. Operators energize long lines from the stronger end, connect shunt reactors with the line, and watch for overvoltage at light load. Cables show the effect at shorter lengths, because waves travel through XLPE insulation at about two-thirds of the speed of light, and their charging current, which can be 20 or more times larger per kilometer, drives a far larger rise through the source impedance.

Voltage Regulation, Voltage Drop, and Losses

Voltage Regulation

Voltage regulation measures how much the receiving-end voltage changes between no load and full load while the sending-end voltage is held constant:

Regulation (%) = (|VR,NL| − |VR,FL|) / |VR,FL| × 100, where |VR,NL| = |VS|/|A|

On a long line, part of the swing between no load and full load is the Ferranti rise, which is why the 300 km example shows 11.7 percent regulation although its sending-end voltage is only 3.7 percent above its receiving-end voltage at full load.

The Approximate Voltage Drop

For a short line, or any series impedance R + jX, take the receiving-end voltage VR as the phase reference. The load draws real power P and reactive power Q per phase, with Q positive for a lagging load, so the line current is I = (P − jQ)/VR. Then

VS = VR + (R + jX)(P − jQ)/VR = VR + (RP + XQ)/VR + j(XP − RQ)/VR

When the quadrature term is small compared with VR, which means that the angle across the impedance is small, the in-phase term accounts for nearly all of the change in magnitude:

ΔV = |VS| − |VR| ≈ (RP + XQ)/VR

The same expression holds with three-phase P and Q and line-to-line voltage, and in per unit, with voltages near 1, it reduces to ΔV ≈ RP + XQ. Dropping the quadrature term understates the drop by about (XP − RQ)2/(2VR3) in per-phase quantities. The approximation ignores shunt capacitance, so it suits short lines and feeders, and it treats a single sending end and receiving end; networks of many buses are the subject of power flow analysis.

The formula shows why reactive power controls voltage on transmission lines. The example line has X/R = 9.3, so where the approximation holds, a megavar of reactive flow moves its voltage about nine times as much as a megawatt of real flow. Distribution conductors have much lower X/R ratios, so real power matters there too, and reversing P, as local generation does, can turn a drop into a rise, the subject of hosting capacity and distribution impacts.

Losses and Efficiency

The real power lost in a three-phase line is 3|I|2R, and its series reactance absorbs 3|I|2X of reactive power, partly offset by its charging. Because |I| = S/(√3 VLL), a short line loses

Ploss = R(P2 + Q2)/VLL2

where P and Q are three-phase quantities and R is the total series resistance. Loss grows with the square of apparent power and falls with the square of voltage: delivering the same real power at a power factor of 0.8 instead of 1.0 multiplies it by (1/0.8)2 = 1.56, and carrying the same load on the same conductor at 345 kV instead of 138 kV divides it by (345/138)2 = 6.25. Efficiency is PR/PS, 96.1 percent in the 300 km example.

Reactive Compensation

Compensation reshapes a line's reactive balance to keep voltage within limits across the range of load.

Shunt Reactors

A shunt reactor absorbs reactive power and cancels part of a line's charging. Extra-high-voltage lines often carry reactors at their terminals, some switched so that they can be removed at heavy load. Reactors limit the Ferranti rise at light load and the overvoltage that follows energizing a line or losing its load.

Shunt Capacitors

Shunt capacitor banks supply reactive power at heavy load, raising voltage and reducing the reactive current in the line, and with it the resistive loss. Their output falls with the square of voltage, so they help least when voltage is lowest. Transmission systems install them at substations, and distribution systems along feeders.

Series Capacitors

A series capacitor cancels part of a line's inductive reactance. With a degree of compensation kse = XC/XL, the net series reactance becomes XL(1 − kse). For a short line, the power transferred at a given angle rises by the factor 1/(1 − kse), so 50 percent compensation doubles it. A series capacitor regulates itself, because its reactive output grows with the square of the line current.

Series capacitors bring three complications. Fault current would overstress the capacitor, so a modern bank has a metal-oxide varistor, a bypass gap or fast switch, and a bypass breaker. The capacitor alters the impedance that a distance relay measures, which power system protection must allow for. And its resonance with the network inductance falls below the power frequency, where it can interact with the torsional modes of turbine-generator shafts, a hazard called subsynchronous resonance.

Compensation and Natural Load

Compensation spread along a line changes its effective constants. Shunt reactors that cancel a fraction ksh of the charging reduce the effective capacitance to Cn(1 − ksh), and series capacitors reduce the effective inductance to L(1 − kse). The compensated natural load is

SIL′ = SIL √((1 − ksh)/(1 − kse))

For the 406 MW example line, 50 percent series compensation raises the natural load to 574 MW, and 60 percent shunt compensation lowers it to 257 MW. The formula treats compensation as evenly distributed, an idealization of equipment installed at a few locations.

Dynamic Compensation

Mechanically switched reactors and capacitors act slowly and in steps. Static VAR compensators, built from thyristor-controlled reactors and thyristor-switched capacitors, and STATCOMs, built on voltage-source converters, adjust continuously within a few cycles; static VAR compensators covers both, including midpoint compensation of long lines. Thyristor-controlled series capacitors bring the same speed to series compensation, and synchronous condensers, which supply both reactive power and fault current, are again being installed on grids that are losing synchronous generation.

Distribution System Structure

A distribution substation steps subtransmission voltage down to primary voltage. North American primaries commonly operate at voltages such as 12.47 kV and 13.2 kV in the 15 kV class, 24.94 kV in the 25 kV class, and 34.5 kV in the 35 kV class, while networks built to IEC practice commonly use 10 kV to 20 kV. Several feeders leave each substation bus, each through a circuit breaker or recloser.

Feeders, Laterals, and Secondaries

A feeder's three-phase main line, the backbone or trunk, runs through its service area. Laterals branch from it, most of them single phase, each protected by a fuse so that a fault interrupts only that lateral's customers. Distribution transformers on poles or pads step down to service voltage. North American residential service is usually 120/240 V single phase from a transformer that serves a handful of customers, on primaries that are mostly four-wire, multigrounded wye systems. European practice uses larger transformers that feed long 230/400 V three-phase networks with many more customers on each.

Radial, Loop, and Network Systems

Most feeders are radial: power flows one way, which keeps protection simple and inexpensive, but a fault interrupts every customer downstream of the device that clears it. Open-loop arrangements join two feeders through a normally open switch, so that healthy sections can be restored from the other side, manually or by automatic fault location, isolation, and service restoration. Underground residential systems often loop pad-mounted transformers this way.

Secondary networks go further. In a grid network, several feeders supply transformers whose secondaries join in a low-voltage mesh, so the loss of one feeder interrupts no customer, and a network protector on each secondary opens when power flows backward into a faulted feeder. Spot networks apply the idea to a single large building. Both serve dense downtown areas, where load density justifies their cost.

Modeling Distribution Lines

Overhead distribution lines are short enough that their shunt capacitance is usually neglected, but they are rarely balanced. Single-phase laterals, uneven loading, and untransposed construction defeat per-phase analysis, so distribution studies use a matrix of phase impedances derived from Carson's equations and solve each phase of the unbalanced feeder, the approach that William H. Kersting develops in Distribution System Modeling and Analysis.

Feeder Voltage Regulation

The Voltage Budget

In North America, service voltage is governed by ANSI C84.1. Its current edition, ANSI C84.1-2020, was approved on March 10, 2020, and covers 60 Hz systems above 100 V, with preferred ratings up to 1,200 kV maximum system voltage. It defines Range A, within which service and utilization voltages should normally fall, and a wider Range B for less frequent excursions. For service voltage on a 120 V system, Range A spans 114 V to 126 V, plus or minus 5 percent.

A distribution engineer divides the width of Range A among the primary feeder, the distribution transformer, the secondary and service conductors, and the bandwidth of the regulating equipment, so that the first customer stays below the upper limit at light load and the last stays above the lower limit at peak load.

Distributed Load

If load is uniform along a feeder of length l, the current falls linearly from the substation to the far end. Integrating the approximate drop gives the same total as the whole load lumped at l/2, and integrating the I2R loss gives the same total as the whole load lumped at l/3. A two-load equivalent, with two-thirds of the load at l/4 and one-third at the far end, reproduces both results.

Worked Example: A 12.47 kV Feeder

An 8 km, 12.47 kV feeder with an illustrative positive-sequence impedance of 0.19 + j0.39 Ω/km serves 6 MW at 0.90 power factor lagging, spread uniformly along its length. Conditions are balanced.

  1. Load: Q = 6 × tan(cos−1 0.90) = 2.906 Mvar, so the substation supplies 6.667 MVA, or 308.7 A.
  2. Drop, with r and x the resistance and reactance per kilometer: ΔV ≈ (rP + xQ)(l/2)/VLL = (0.19 × 6 + 0.39 × 2.906) × 4/12.47 = 0.729 kV, or 5.85 percent, which is 7.0 V on a 120 V base. The same load lumped at the end would drop twice as much. A phasor calculation of the midpoint equivalent at constant current gives 5.95 percent, so the approximation runs 0.1 percentage point low.
  3. Loss: rlS2/(3VLL2) = 0.19 × 8 × 6.6672/(3 × 12.472) = 0.1448 MW, or 2.4 percent of the load.
  4. Capacitor bank: a 1,800 kvar bank two-thirds of the way out, at 5.33 km, reduces the end-of-feeder drop to 3.44 percent, or 4.1 V on a 120 V base, and cuts the loss by 24.3 kW, or 16.8 percent.

The location follows the two-thirds rule: for a uniformly distributed reactive load, one bank rated at two-thirds of the reactive load and placed two-thirds of the way out removes eight-ninths of the loss caused by reactive current, here from 27.5 kW to 3.1 kW with a 1,937 kvar bank. The rule assumes a uniform, constant load on a uniform conductor, so placement studies start from it rather than end with it. At the end of the feeder, the 1,800 kvar bank would leave a smaller drop, 2.24 percent, but save only 19.5 kW, because its output would flow back toward the substation over much of the feeder.

Regulating Equipment

Utilities regulate feeder voltage with three kinds of equipment. A load tap changer on the substation transformer adjusts its ratio under load; the mechanism belongs to the study of power transformers. A step-voltage regulator, an autotransformer with its own tap changer installed on the feeder, usually provides a range of plus or minus 10 percent in 32 steps of 0.625 percent, or 0.75 V on a 120 V base. Its controller holds voltage within a bandwidth around a set point and waits out a time delay before changing taps so that it does not chase brief fluctuations. With line-drop compensation, it regulates the estimated voltage at a downstream load center, computed from the measured current and from resistance and reactance settings that model the feeder. Cascaded regulators are usually given longer delays downstream, so that the upstream unit acts first.

The third kind is the capacitor bank. Fixed banks supply the base reactive load, and switched banks add capacity at peak under controls that respond to time, temperature, voltage, reactive power, or current. Volt/VAR optimization coordinates all three, often holding voltage in the lower part of the permitted band so that voltage-sensitive loads draw less energy, a practice called conservation voltage reduction. Distributed generation complicates each of these controls by reversing power flow.

Cable Charging Current and Ampacity

Charging Current

A single-core cable is a coaxial capacitor. With the conductor screen at diameter d and the outer surface of the insulation at diameter D, its capacitance per unit length is

C = 2πε0εr / ln(D/d)

and each phase draws a charging current of ωCVph per unit length. Consider an illustrative 230 kV XLPE cable at 60 Hz, with d = 50 mm, D = 96 mm, and εr = 2.3:

  1. Capacitance: C = 2π × 8.854 × 10−12 × 2.3/ln(96/50) F/m = 0.1962 µF/km, about 22 times that of a 230 kV overhead line built with the conductor of the earlier example on a flat 6 m spacing.
  2. Charging current: Ic = ωCVph = 2π × 60 × 0.1962 × 10−6 × 132,790 = 9.82 A/km.
  3. Reactive power: Q = ωCVLL2 = 3.91 Mvar/km, or about 156 Mvar for a 40 km circuit.
  4. Critical length: if the conductor is rated at an illustrative 1,000 A and all of the charging is supplied from one end, charging alone uses the whole rating at 1,000/9.82 = 102 km; supplying half of the charging from each end doubles that length to 204 km.
  5. Remaining capacity: a 40 km cable charged from one end carries 393 A of charging current at its sending terminal, nearly in quadrature with the load current, so √(1,0002 − 3932) = 920 A, about 92 percent of the rating, remains for load.

As a coaxial line with the return current in its screen, the cable has a surge impedance of about 26 Ω and an SIL near 2,050 MW, against about 400 MVA for its 1,000 A rating. Cross-bonded circuits have more inductance, set by phase spacing, but a natural load still well above their rating. A cable therefore generates net reactive power at any practical load, which is why long AC cable circuits need shunt reactors and long submarine links use direct current.

Ampacity of Overhead Conductors

Ampacity is the current a conductor can carry continuously without exceeding a temperature limit. For a bare overhead conductor, the limit guards against annealing, which permanently weakens aluminum held too hot for too long, and against sag that brings the conductor too close to the ground. IEEE 738-2023 gives a numerical method that relates a bare conductor's core and surface temperatures to its steady or time-varying current and to the weather, through a heat balance of Joule and solar heating against convective and radiative cooling. It leaves the choice of weather and conductor parameters to the user. Because wind cooling dominates, a rating built on conservative weather assumptions can sit well below what a conductor could carry on a cool, breezy day, which motivates ambient-adjusted and dynamic line ratings.

Ampacity of Underground Cables

A buried cable sheds its heat through a chain of thermal resistances: its insulation, its coverings, and the soil, which usually dominates. IEC 60287-1-1:2023 gives current rating equations and loss calculations for steady-state operation at 100 percent load factor, for cables buried directly, in ducts, troughs, or steel pipes, and in air. For AC cables where the soil does not dry out, the permissible current is

I = [(Δθ − Wd(0.5T1 + n(T2 + T3 + T4))) / (RT1 + nR(1 + λ1)T2 + nR(1 + λ1 + λ2)(T3 + T4))]1/2

where Δθ is the permissible rise of conductor temperature above ambient, R is the AC resistance per unit length at maximum operating temperature, Wd is the dielectric loss per unit length, T1 through T4 are the thermal resistances per unit length of the insulation, bedding, outer covering, and surroundings, n is the number of load-carrying conductors in the cable, and λ1 and λ2 are the sheath and armor losses as fractions of the conductor loss. North American practice traces the same thermal-circuit approach to a 1957 AIEE paper by J. H. Neher and M. H. McGrath, and the U.S. National Electrical Code permits ampacities calculated this way under engineering supervision.

Three practical factors often decide the rating. Soil around a hot cable can dry out, which raises its thermal resistivity and traps more heat, a runaway that engineered backfill is used to prevent. Neighboring circuits heat one another. And the sheaths of single-core cables carry induced voltage: bonding both ends lets circulating current flow and adds loss, single-point bonding leaves a standing voltage at the open end, and cross-bonding transposes the sheath connections at joints so that induced voltages cancel over each major section. XLPE insulation is commonly rated for a continuous conductor temperature of 90 °C.

Summary

A line's behavior follows from its parameters per unit length. Resistance sets loss, inductance through ln(GMD/GMR) sets the reactance that governs voltage drop and power transfer, and capacitance through ln(GMD/r) sets the charging current. Transposition equalizes the phases, and bundling lowers inductance, raises capacitance, and controls corona.

The short-line model ignores charging, the nominal π circuit suits medium lengths, and the exact solution in cosh γl and sinh γl covers any length. Surge impedance loading, VLL2/Zc, marks the load at which a line neither supplies nor absorbs net reactive power, and the Ferranti effect raises the voltage at the open end of a line by about (βl)2/2. Reactors, capacitors, and power electronic compensators reshape that balance, and the St. Clair curve turns SIL into a planning estimate of loadability.

Distribution trades electrical length for scale and imbalance. The approximate drop (RP + XQ)/V, the half-length and third-length rules, and the two-thirds rule for capacitors let an engineer size a feeder quickly, while tap changers, regulators, and capacitor banks hold service voltage within ANSI C84.1. For cables, charging current and heat, rather than voltage drop, set the practical limits.

Related Topics