Electronics Guide

Synchronous Machines

A synchronous machine is an AC machine whose rotor turns in step with the rotating magnetic field of its stator currents. The rotor carries a DC field winding or permanent magnets, so it needs no induced current to produce torque, and in steady state its speed is fixed by the supply frequency and the number of poles. The generators of steam, gas, and hydroelectric power stations are, with few exceptions, synchronous machines. The same machine can run as a constant-speed motor or, with no mechanical load, as a synchronous condenser that only supplies or absorbs reactive power.

The machine offers two independent controls. The prime mover, or the mechanical load, sets the real power; the field current sets the internal voltage and, with it, the reactive power. A generator can therefore export reactive power to support the network voltage, or absorb it when the voltage runs high, while turning at exactly synchronous speed. A squirrel-cage induction machine has no such control, because it must draw its magnetizing current from the supply; AC Induction Motor Drives describes its equivalent circuit.

This article covers three-phase machines with electrically excited fields, with briefer sections on transient reactances, excitation systems, and permanent-magnet machines. It assumes balanced operation in sinusoidal steady state. Voltages and currents are RMS phasors, per-phase equations use line-to-neutral voltages, and power means three-phase power. Per-unit quantities are on the machine's own rating, as described in Per-Unit System and One-Line Diagrams. Armature resistance, a small fraction of the synchronous reactance in large machines, is neglected in the power relations.

Construction

An electrically excited synchronous machine has two windings. The armature winding carries the AC power and, in all but small machines, sits on the stator. The field winding carries direct current, sets up the main magnetic field, and sits on the rotor. Only the excitation power, a small fraction of the rating, then has to reach the rotating part, while the large armature currents and high voltages stay in stationary conductors that are easy to insulate, brace, and cool.

Stator and Armature Winding

The stator core is a stack of thin, insulated electrical-steel laminations, which limit eddy-current loss. Slots on its inner surface hold a three-phase winding distributed over many slots, with the phases displaced 120 electrical degrees around the air gap. Large machines use preformed coils or bars with mica-based insulation. Generator phases are normally connected in wye, and the neutral is often grounded through an impedance that limits ground-fault current.

Round and Salient-Pole Rotors

The field winding receives direct current through slip rings and brushes or from a brushless exciter on the shaft, and it creates alternate north and south poles. The form of the rotor follows its speed. Steam and gas turbines are high-speed machines, so their generators have two or four poles and a round, or cylindrical, rotor: a solid alloy-steel forging with axial slots for the field winding, which wedges hold along the body and retaining rings hold at the ends. Centrifugal stress limits the diameter of a rotor turning at 3,600 or 3,000 revolutions per minute, so turbo-generators are long and slender, and their nearly uniform air gap gives them almost the same magnetic properties along every axis.

Hydraulic turbines and large engines turn slowly, so their generators need many poles. Their rotors have salient poles: laminated pole bodies that project from a rim, each with a concentrated field coil, on a rotor that is wide in diameter and short along its axis. The air gap is short over the pole faces and long between them, so flux passes more easily along the pole axes. That property is saliency.

Damper Windings and Cooling

Salient-pole rotors usually carry a damper, or amortisseur, winding: bars in the pole faces joined by end rings, like the cage of an induction motor. In balanced steady state it carries no current, because the stator field does not move relative to it. When the rotor swings, or when unbalanced stator currents create a backward-rotating field, currents induced in the damper oppose the change. In a round rotor, eddy currents in the solid body and the slot wedges do much of the same work.

Smaller machines are air-cooled. Large turbo-generators are commonly filled with hydrogen, whose low density and high thermal conductivity cut windage loss and improve heat transfer compared with air, and the largest units also pass water through hollow conductors in their stator bars.

The Rotating Magnetic Field and Synchronous Speed

A winding carrying current produces a magnetomotive force (MMF), the ampere-turns that drive flux around a magnetic path, as Ampère's law in Magnetostatics describes. One phase carrying alternating current produces an MMF wave that is fixed in position and pulsates in amplitude.

How Three Phases Produce a Rotating Field

Measure the electrical angle θ around the air gap from the axis of phase a, and keep only the fundamental, sinusoidal part of each winding's MMF. With balanced currents, phase a produces Fa = Fm cos ωt cos θ, where Fm is proportional to the peak current and to the winding's effective turns. Phases b and c give the same expression with both ωt and θ reduced by 120° and 240°, respectively. Writing each product of cosines as half the sum of two cosines gives each phase a forward term, ½Fm cos(θ − ωt), and a backward term; the three backward terms are 120° apart and sum to zero. The total is

F(θ, t) = (3/2) Fm cos(θ − ωt)

The wave has a constant peak 1.5 times that of one phase, located at θ = ωt. Interchanging any two supply leads reverses the phase sequence and the direction of rotation. Unbalanced currents add a backward-rotating wave, the negative-sequence field treated in Fault Analysis and Symmetrical Components.

Synchronous Speed

A machine with P poles, always an even number, has P/2 pole pairs. The field advances one pole pair per cycle of the supply, and electrical and mechanical angles are related by θe = (P/2)θm. The synchronous speed in revolutions per minute (rpm) is

ns = 120 f / P

where f is the frequency in hertz and P is the number of poles, not pole pairs; 120 is 60 seconds per minute times 2 poles per pair. In radians per second, ωsm = 4πf/P. Conversely, a generator with P poles driven at n rpm produces f = Pn/120 hertz.

Synchronous Speed for Common Pole Numbers
Poles Speed at 60 Hz (rpm) Speed at 50 Hz (rpm)
23,6003,000
41,8001,500
61,2001,000
12600500
24300250
48150125
7210083.3

Two-pole machines serve most steam and gas turbines, and four-pole machines the half-speed turbines of many nuclear plants. Hydro-generators, whose speed suits the turbine and the head at the site, have many more poles.

Why Torque Requires Synchronous Speed

The DC field turns with the rotor, so steady torque arises only when the rotor and stator fields turn together at a constant angle. At any other speed the angle between them changes continuously and the torque averages zero, which is why a synchronous motor needs a separate means of starting.

The Generated Voltage

The EMF Equation

Drive the rotor at synchronous speed with the field excited and the armature open, and suppose the rotor produces a sinusoidally distributed flux Φ per pole. The flux linking a concentrated, full-pitch winding of N turns varies as NΦ cos ωt, and Faraday's law gives an induced voltage of ωNΦ sin ωt, with an RMS value of ωNΦ/√2. A real phase winding is spread over several slots, and its coils usually span less than a pole pitch, so its coil voltages are slightly out of phase and their sum is reduced by a winding factor kw. The RMS voltage per phase is

Ef = √2 π f N kw Φ ≈ 4.44 f N kw Φ

where N is the number of series turns per phase and Φ is in webers. Ef is called the excitation, internal, or open-circuit voltage. Below saturation, Φ is proportional to the field current If, so Ef is proportional to both speed and field current.

Distribution and Pitch Factors

The winding factor is kw = kdkp. The distribution factor accounts for the coils of a phase lying in q adjacent slots per pole, each displaced by the slot angle γ in electrical degrees:

kd = sin(qγ/2) / [q sin(γ/2)]

The pitch factor accounts for coils that span a fraction ρ of a pole pitch:

kp = sin(ρ × 90°)

For the hth space harmonic, replace γ with hγ and 90° with h × 90°. A pitch of 5/6 keeps a pitch factor of 0.966 for the fundamental but cuts the fifth and seventh harmonics to 0.259 of their full-pitch values. Third-harmonic voltages are in phase in all three phases, so they cancel in the line-to-line voltages of a wye-connected winding.

A Numerical Example

A four-pole, 60 Hz machine has 48 stator slots and a double-layer winding with coils spanning 10 slots. A pole pitch is 12 slots, so ρ = 5/6; q = 48/(4 × 3) = 4 slots per pole per phase; and γ = 180° × 4/48 = 15° electrical.

  1. kd = sin 30° / (4 sin 7.5°) = 0.9577 and kp = sin 75° = 0.9659, so kw = 0.9250.
  2. With 4 turns per coil and all 16 coils of each phase in series, N = 64 turns.
  3. For a flux of 0.0175 Wb per pole, Ef = 4.443 × 60 × 64 × 0.9250 × 0.0175 = 276 V per phase, or 478 V line-to-line, at 1,800 rpm.

Synchronous Reactance and the Per-Phase Equivalent Circuit

Armature Reaction

Balanced armature current produces its own MMF, rotating at synchronous speed with the rotor, so the air-gap flux, and the voltage Er it induces, differ from those of the field alone. This armature reaction induces a voltage proportional to the armature current and lagging it by 90°, as an inductive reactance does, so it is represented by a reactance Xa: Er = Ef − jXaIa in the generator convention defined below. Leakage flux that links the armature without crossing the air gap adds a leakage reactance Xl, and the two form the synchronous reactance:

Xs = Xl + Xa

Saturation affects mainly Xa, which is why the synchronous reactance at rated voltage is smaller than its unsaturated value. In a round rotor the direct- and quadrature-axis reactances are nearly equal, and Xs is the direct-axis synchronous reactance Xd that fault studies use for sustained current. Schneider Electric's Cahier Technique no. 158 gives typical values of 1.50 to 2.30 per unit for turbo-generators and 0.70 to 1.20 per unit for salient-pole generators, as tabulated in Per-Unit System and One-Line Diagrams.

Generator and Motor Conventions

In the generator convention, the armature current Ia flows out of the machine, and the per-phase circuit is Ef in series with the armature resistance Ra and jXs:

Ef = Vt + (Ra + jXs) Ia

where Vt is the terminal voltage per phase. In the motor convention, Ia flows into the machine, and

Vt = Ef + (Ra + jXs) Ia

The direction of real power, not the circuit, distinguishes generating from motoring. The model assumes balanced sinusoidal steady state, a linear magnetic circuit, and a round rotor.

Phasor Diagrams

Take Vt as the reference, neglect Ra, and let a generator deliver Ia at a power factor angle φ, positive when the current lags Vt. The drop jXsIa leads Ia by 90°, and adding it to Vt places Ef ahead of Vt by the power angle δ, also called the load angle or torque angle. Resolving along and across Vt gives

Ef cos δ = Vt + XsIa sin φ

Ef sin δ = XsIa cos φ

  • Lagging power factor (φ > 0): Ef cos δ exceeds Vt. The machine is overexcited and delivers reactive power.
  • Unity power factor (φ = 0): Ef = √[Vt2 + (XsIa)2].
  • Leading power factor (φ < 0): Ef cos δ is less than Vt. The machine is underexcited and absorbs reactive power.

In the motor convention Ef = Vt − jXsIa, so the Ef of a motor lags Vt by δ. An overexcited motor draws leading current and supplies reactive power to the network, as an overexcited generator does.

The relations also give the voltage regulation: the rise in terminal voltage when full load is removed at constant field current, as a fraction of rated voltage. A machine with Xs = 1.60 per unit delivering rated current at 0.85 power factor lagging has Ef = 2.29 per unit, a linear-model regulation of 129 percent. Saturation keeps the actual rise far smaller.

Open-Circuit and Short-Circuit Tests

Two tests at rated speed, one with the armature open and one with it short-circuited, give the synchronous reactance and the short-circuit ratio.

The Open-Circuit Characteristic

With the armature open, the field current is raised in steps and the terminal voltage is recorded. The open-circuit characteristic, or open-circuit saturation curve, starts along a straight line, the air-gap line, on which nearly all the field MMF drives flux across the air gap. It bends below that line as the iron saturates.

The Short-Circuit Characteristic

With the terminals shorted through ammeters, the field current is raised until the armature current reaches about its rated value. The machine's own impedance is almost purely reactive, so the current lags Ef by nearly 90° and its armature reaction directly opposes the field. The net air-gap flux stays small, the iron stays unsaturated, and the short-circuit characteristic is almost a straight line.

Synchronous Reactance and Short-Circuit Ratio

At a given field current, the unsaturated synchronous reactance Xd(unsat) is the air-gap-line voltage divided by the short-circuit current. The short-circuit ratio (SCR) is the field current for rated voltage on the open-circuit characteristic divided by the field current for rated current on the short-circuit characteristic. Because the short-circuit characteristic is linear, the SCR equals the per-unit short-circuit current at the field current that gives rated open-circuit voltage, so

Xd(sat) ≈ 1 / SCR

in per unit, where the saturated synchronous reactance Xd(sat) suits calculations near rated voltage. Consider illustrative results for a 100 MVA, 13.8 kV, 60 Hz round-rotor generator, with a rated current of 4,184 A and a base impedance of 13.82/100 = 1.9044 Ω. The air-gap line reaches rated voltage at a field current of 400 A and the open-circuit characteristic at 460 A, and the short-circuit characteristic reaches rated current at 736 A.

  1. Unsaturated reactance. At 736 A the air-gap line gives 736/400 = 1.84 per unit of voltage while the short circuit carries 1.00 per unit of current, so Xd(unsat) = 1.84 per unit, or 3.50 Ω per phase.
  2. Short-circuit ratio. SCR = 460/736 = 0.625.
  3. Saturated reactance. Xd(sat) ≈ 1/0.625 = 1.60 per unit, or 3.05 Ω per phase.

Both values fall in the Cahier Technique range for turbo-generators, and the examples below use Xs = 1.60 per unit for this machine. A high SCR, meaning a low synchronous reactance, raises the power a machine can carry before its stability limit and reduces its voltage change with load, at the cost of a longer air gap, more field ampere-turns, and a larger machine.

Other Tests and the Standards

A zero-power-factor test, with the generator delivering rated current to an inductive load, separates leakage reactance from armature reaction and yields the Potier reactance. A slip test gives the quadrature-axis reactance of a salient-pole machine: with the field open and a reduced balanced voltage applied, the rotor is driven slightly off synchronous speed, and the ratio of voltage to current swings between Xd and Xq. A sudden short circuit gives the transient and subtransient quantities described later.

IEEE 115-2019, the IEEE Guide for Test Procedures for Synchronous Machines Including Acceptance and Performance Testing and Parameter Determination for Dynamic Analysis, was published in March 2020, and IEEE has authorized its revision. Standstill frequency response testing, which identifies dynamic-model parameters without rotating the machine, was first standardized in IEEE 115A-1987, a supplement to the 1983 edition of IEEE 115. The IEC counterpart, IEC 60034-4-1:2018, describes methods for three-phase machines rated 1 kVA and larger whose field winding is supplied through slip rings and brushes. It notes that brushless machines need special effort for some tests and that its tests apply only in part to permanent-magnet machines, which must be protected against irreversible demagnetization.

The Power-Angle Relationship

From here on, P denotes real power rather than the number of poles.

Real Power

Let δ be the angle by which Ef leads Vt. Multiplying the second phasor relation by Vt/Xs gives the real power per phase, VtIa cos φ = VtEf sin δ / Xs. For three phases, with per-phase RMS voltages,

P = 3 Vt Ef sin δ / Xs

In per unit the factor 3 disappears. This is the transfer relation P = V1V2 sin δ / X of Power System Analysis, with the internal voltage as bus 1 and the terminals as bus 2, and the sign convention is the same: a positive δ, with Ef leading, means that the machine is generating, and a negative δ that it is motoring. Through an external reactance Xe to a network voltage V, the same form holds with V in place of Vt, Xs + Xe in place of Xs, and δ taken as the angle by which Ef leads V.

The torque is T = P/ωsm. The angle δ is electrical; the rotor is displaced by δ divided by the number of pole pairs, so a 72-pole hydro-generator at a power angle of 38° runs only about 1.06 mechanical degrees ahead of its no-load position.

Reactive Power

Resolving along Vt gives the reactive power delivered at the terminals:

Q = 3 Vt (Ef cos δ − Vt) / Xs

A generator supplies reactive power when Ef cos δ exceeds Vt, the overexcited condition, and absorbs it otherwise. This is the machine form of the pairing, noted in Power Flow Analysis, of real power with angle and reactive power with voltage magnitude.

Pull-Out Power and the Steady-State Stability Limit

At fixed Ef and Vt, the power-angle curve peaks at the pull-out power, 3VtEf/Xs, when δ = 90°. Its slope is the synchronizing power coefficient:

Ps = dP/dδ = 3 Vt Ef cos δ / Xs

Below 90° the slope is positive: if the rotor advances slightly, the electrical power rises and pulls it back, so the machine is stable against small, slow changes. Beyond 90° an advance lowers the electrical power, the rotor gains on the field, and the machine pulls out of step. With constant field current, the steady-state stability limit of a round-rotor machine connected directly to an infinite bus is therefore δ = 90°. Operators keep a margin below it, and because the limiting power rises with Ef, an underexcited machine is less secure. The response to large, sudden disturbances, such as a fault, also depends on rotor inertia and clearing time; power system stability studies analyze it with the swing equation.

Generator Operation on an Infinite Bus

An infinite bus is an idealized network whose voltage magnitude and frequency do not change, whatever power a machine exchanges with it; a generator on a large interconnection behaves nearly this way. With terminal voltage and speed fixed, the prime mover and the field current remain the only controls.

Synchronizing

Before its breaker closes, an incoming generator must match the network in phase sequence, frequency, voltage magnitude, and phase angle; closing with a large angle or voltage difference causes a current surge and a torque shock. An automatic synchronizer, or a synchroscope with a synchronism-check relay, governs the closing, as Hydroelectric Power Electronics describes. Grid-tied converters solve the equivalent problem with phase-locked loops, as Grid Synchronization and Control explains.

Controlling Real Power

After an ideal synchronization, Ef equals Vt and the machine carries no current. Opening the turbine's valves or wicket gates raises the mechanical torque; the rotor advances until the electrical power matches the input, and the machine settles at synchronous speed with a larger δ. The governor setpoint thus controls real power. At constant field current, raising the real power also lowers the reactive power, because Ef cos δ falls as δ grows.

Controlling Reactive Power

At constant mechanical power, Ef sin δ is fixed, so the tip of the Ef phasor moves along a line parallel to Vt. Raising the field current lengthens Ef, reduces δ, and raises Ef cos δ, so the machine delivers more reactive power. Lowering it does the reverse until the machine absorbs reactive power and, at δ = 90°, reaches its stability limit.

Worked Example

The generator of the test example, with Xs = 1.60 per unit on its 100 MVA rating, is connected to an infinite bus at its terminals, Vt = 1.0 per unit, and delivers 80 MW and 40 Mvar. The base current is 4,184 A, and the base phase voltage is 13.8/√3 = 7.967 kV.

  1. Power. P = 0.80 and Q = 0.40 per unit, so the power factor is 0.80/√(0.802 + 0.402) = 0.894 lagging.
  2. Current. With Vt as reference, Ia = (S/Vt)* = 0.80 − j0.40 = 0.8944 e−j26.57° per unit, or 3,742 A.
  3. Excitation voltage. Ef = Vt + jXsIa = 1.0 + j1.60(0.80 − j0.40) = 1.64 + j1.28 = 2.0804 ej37.97° per unit. The excitation voltage is 2.0804 × 7.967 = 16.58 kV per phase, and the power angle is 37.97°.
  4. Check. P = 2.0804 sin 37.97° / 1.60 = 0.800 per unit, and Q = (2.0804 cos 37.97° − 1.0) / 1.60 = 0.400 per unit.
  5. Stiffness. The synchronizing power coefficient is 2.0804 cos 37.97° / 1.60 = 1.025 per unit per radian, or 1.79 MW per electrical degree.

Holding 80 MW and treating Ef as proportional to field current, as the linear model allows, gives the operating points in the table.

Effect of Field Current on the Example Generator at 80 MW
Field current Ef (per unit) δ Q (per unit) Ia (per unit) Power factor
110 percent of base case2.28834.01°0.5610.9770.819 lagging
Base case2.08037.97°0.4000.8940.894 lagging
90 percent1.87243.13°0.2290.8320.961 lagging
70 percent1.45661.52°−0.1910.8220.973 leading
61.5 percent (stability limit)1.28090.00°−0.6251.0150.788 leading

A 10 percent increase in field current raises the reactive output by 40 percent and the armature current by 9 percent. Cutting the field current to 70 percent turns the machine from a source of 40 Mvar into a sink of 19 Mvar. The least excitation that can carry 80 MW is Ef = PXs/Vt = 1.28 per unit. If instead the governor raises the output to 90 MW at the base-case field current, δ grows to 43.80° and Q falls to 0.313 per unit.

V-Curves

Plotting armature current against field current at constant real power gives the V-curves. Each has its minimum, Ia = P/Vt, at unity power factor, where Ef = √[Vt2 + (PXs/Vt)2]. To the right of the minimum the machine is overexcited and delivers reactive power; to the left it is underexcited, until the curve ends at the stability limit, Ef = PXs/Vt. The table gives points for the example machine, with Ef standing in for field current; beyond the limit no steady operating point exists.

Armature Current in Per Unit on V-Curves of the Example Generator (Xs = 1.60, Vt = 1.0 per unit)
Ef (per unit) P = 0 P = 0.5 per unit P = 0.8 per unit
0.500.313Beyond limitBeyond limit
1.000.0000.559Beyond limit
1.250.1560.501Beyond limit
1.500.3130.5270.812
2.000.6250.7220.867
2.500.9380.9911.074

The minima fall at Ef = 1.00, 1.28, and 1.62 per unit. At zero real power the machine is a synchronous condenser drawing |Ef − Vt|/Xs.

The Capability Curve

A generator's capability curve bounds the real and reactive power it can deliver continuously at rated terminal voltage. In per unit, squaring and adding the power-angle expressions for P and for Q + Vt2/Xs gives

P2 + (Q + Vt2/Xs)2 = (VtEf/Xs)2

so at constant excitation the operating point moves on a circle centered at P = 0, Q = −Vt2/Xs. With real power on the horizontal axis and reactive power on the vertical axis, positive for overexcited operation, the limits are as follows.

Armature Current Limit

Stator winding temperature limits the armature current. At rated voltage, constant current means constant apparent power, so the limit is a circle about the origin with a radius of rated MVA, 1.0 per unit.

Field Current Limit

Rotor winding temperature limits the field current, and with it Ef, to the constant-excitation circle through the rated operating point, where the machine delivers rated MVA at rated power factor. If the example machine is rated at 0.85 power factor lagging, its rated point has Ef = 2.290 per unit at δ = 36.43°, so the field limit is a circle centered at Q = −0.625 per unit with a radius of 1.431 per unit. At zero real power it allows 0.806 per unit of reactive output, less than the armature could carry. Above rated real power the armature limit governs: at P = 0.95 per unit it allows 0.312 per unit of reactive power, against 0.446 per unit for the field. The limits meet at the rated point because the field winding is designed for the excitation that point requires.

Underexcited Limits

The theoretical steady-state stability limit, δ = 90°, is the line Q = −Vt2/Xs, or −0.625 per unit for the example machine, when the machine connects directly to an infinite bus. With an external reactance Xe, it becomes a circle centered at Q = (Vt2/2)(1/Xe − 1/Xs) with a radius of (Vt2/2)(1/Xe + 1/Xs), whose lower arc rises with real power and shrinks the stable underexcited region at high output. Behind Xe = 0.20 per unit, the example machine's limit rises from Q = −0.625 per unit at zero output to −0.477 per unit at P = 0.90 per unit. Both forms assume constant field current; a continuously acting voltage regulator can extend the practical limit.

The second limit is thermal. When a generator is underexcited, the low field current leaves the rotor retaining rings less saturated, and the end-winding leakage fluxes of stator and rotor combine to raise the axial flux entering the end packets of the stator core, where eddy currents heat the laminations. This core-end heating can severely restrict underexcited operation, particularly in round-rotor machines, and an underexcitation limiter in the excitation system keeps the machine inside both limits.

Prime Mover Limit

The turbine's maximum output adds a vertical line, and some turbines also have a minimum stable output. Hydrogen-cooled generators have one curve for each hydrogen pressure.

Synchronous Motors

A synchronous motor is the same machine with power flowing the other way. In the motor convention Ef lags Vt, and the power drawn is 3VtEf sin δ / Xs, with δ measured as the lag of Ef, so that it is positive when motoring. The motor runs at synchronous speed at any load up to its pull-out torque,

Tmax = 3 Vt Ef / (ωsm Xs)

beyond which it falls out of step and its protection trips it. Raising the field current raises the pull-out torque as well as the reactive power supplied. Constant speed and adjustable power factor suit synchronous motors to large, steadily loaded compressors, pumps, fans, and mills.

Starting

At standstill the stator field sweeps past the poles too quickly for the rotor to follow, so the motor must be brought near synchronous speed by other means.

  • Induction starting. A line-started motor accelerates as an induction motor on its damper winding, with the field winding short-circuited through a discharge resistor to limit the high voltage that the slipping stator field would induce in its many turns. Near synchronous speed the controller applies direct current to the field, and the rotor pulls into step; the largest load torque at which the motor can pull its connected inertia into step is the pull-in torque. Reduced-voltage starting limits inrush current where the supply is weak.
  • Variable-frequency starting. A converter raises the stator frequency from near zero along with the rotor, keeping the machine synchronized. Pumped-storage units in pumping mode start this way, as do gas-turbine generators, which run as motors to accelerate their turbines, and motors that run permanently from a drive.
  • Auxiliary motor. A small pony motor accelerates the unloaded machine, a method found mainly on older installations.

Power Factor Correction and Synchronous Condensers

An overexcited synchronous motor supplies reactive power while it drives its load. Suppose a plant draws 1,500 kW at 0.80 power factor lagging, or 1,125 kvar, and a new synchronous motor drawing 300 kW is to raise the plant's power factor to 0.95 lagging.

  1. The plant will draw 1,800 kW, so at 0.95 power factor its reactive demand can be at most 1,800 × tan(cos−1 0.95) = 591.6 kvar.
  2. The motor must supply the difference, 1,125 − 591.6 = 533.4 kvar.
  3. The motor therefore runs at √(3002 + 533.42) = 612 kVA, at a power factor of 0.49 leading.

At unity power factor the same motor would leave the plant at 0.85 lagging. The motor must be rated, and its field winding sized, for the leading duty.

A synchronous condenser is a synchronous motor with no mechanical load, operating on the zero-power V-curve. Unlike a capacitor bank, whose output falls with the square of the voltage, a condenser under voltage control raises its output when the voltage sags, and it adds inertia and short-circuit current. Condensers are again being installed where the retirement of synchronous generation has weakened the network, sometimes beside converter-based compensators, as Static VAR Compensators describes.

Salient-Pole Machines and Two-Reaction Theory

In a salient-pole machine, an armature MMF aligned with the poles meets the short air gap and produces more flux than the same MMF aligned between them, so one synchronous reactance cannot describe the machine. Two-reaction theory, which originated with the French engineer André Blondel and which R. E. Doherty and C. A. Nickle extended in their 1926 paper “Synchronous Machines I: An Extension of Blondel's Two-Reaction Theory,” resolves the armature current into two components:

  • A direct-axis component Id, whose MMF acts along the pole axis, the d-axis, through the direct-axis synchronous reactance Xd.
  • A quadrature-axis component Iq, whose MMF acts midway between the poles, along the q-axis, through the smaller quadrature-axis synchronous reactance Xq.

In the usual convention the q-axis leads the d-axis by 90 electrical degrees, and Ef lies along the q-axis. With Ra neglected and the generator convention,

Ef = Vt + jXdId + jXqIq

where Id and Iq are the phasor components of Ia along the two axes. Because the q-axis direction is unknown until δ is found, the diagram is built in two steps: the phasor Vt + jXqIa lies along the q-axis and gives δ, and Ef equals its magnitude plus (Xd − Xq) times the magnitude of Id whenever Ia lags Ef, which includes every lagging power factor. The real power in per unit becomes

P = (VtEf/Xd) sin δ + (Vt2/2)(1/Xq − 1/Xd) sin 2δ

and the reactive power delivered is

Q = (VtEf/Xd) cos δ − Vt2(cos2 δ / Xd + sin2 δ / Xq)

For three-phase power in physical units, multiply both by 3 and use per-phase voltages; with Xd = Xq, both reduce to the round-rotor forms. The second term of P is reluctance power, present even with no field current. It peaks at δ = 45° and adds to the excitation term below 90°, so the curve peaks, and the steady-state stability limit falls, below 90°.

Consider an illustrative salient-pole generator with Xd = 1.00 and Xq = 0.60 per unit that delivers P = 0.80 and Q = 0.40 per unit at Vt = 1.0 per unit. Then Vt + jXqIa = 1.0 + j0.60(0.80 − j0.40) = 1.24 + j0.48 = 1.3297 ej21.16°, so δ = 21.16°. The d-axis current has a magnitude of 0.6618 per unit, and Ef = 1.3297 + 0.40 × 0.6618 = 1.5944 per unit. The excitation term supplies 0.576 per unit of the power and the reluctance term 0.224. At this excitation the curve peaks at 1.713 per unit at δ = 70.85°, and with the field lost the reluctance term alone could carry 0.333 per unit at 45°. Treating the machine as round-rotor with Xs = Xd gives a similar Ef, 1.6125 per unit, but a power angle of 29.74°, about 8.6° too large.

Synchronous reluctance motors have no field winding and run on reluctance torque alone. R. H. Park's 1929 paper in the Transactions of the American Institute of Electrical Engineers, “Two-Reaction Theory of Synchronous Machines: Generalized Method of Analysis, Part I,” transformed the phase quantities onto rotating d- and q-axes. That rotor reference frame underlies both the dynamic models of power system studies and the field-oriented control of drives.

Transient and Subtransient Reactances

After a sudden change, such as a short circuit, the flux linking the closed rotor circuits cannot change instantly. Currents induced in the damper and field windings oppose the change and force the armature flux into paths of higher reluctance, so the machine at first presents a much smaller reactance. Fault studies represent the decay with three direct-axis reactances, which Fault Analysis and Symmetrical Components uses in its calculations:

  • Subtransient reactance, X″d, governs the first few cycles, while the damper currents persist. Its extra current decays with the short-circuit subtransient time constant T″d.
  • Transient reactance, X′d, governs the following period, while the field winding still opposes the change. Its extra current decays with the short-circuit transient time constant T′d.
  • Synchronous reactance, Xd, governs the sustained current once both effects have died away, with the excitation held constant.

That article's assumed values, X″d = 0.15, X′d = 0.25, and Xd = 1.6 per unit on the machine rating, with T″d = 0.035 s and T′d = 0.9 s, show the scale: a three-phase short circuit at the terminals of the unloaded machine starts at 6.67 per unit of symmetrical current and decays toward 0.625 per unit, below rated current. The open-circuit time constants are longer by roughly the ratios of the reactances: T′d0 ≈ T′dXd/X′d = 5.8 s and T″d0 ≈ T″dX′d/X″d = 0.058 s for these values. These classical approximations neglect armature resistance, apply to a short circuit at the terminals, and assume that the subtransient decay ends long before the transient decay, as here, where T′d is about 26 times T″d.

Quadrature-axis counterparts, X″q and X′q, follow from the same argument; a laminated salient-pole rotor has no quadrature-axis circuit comparable to the field, so its X′q equals Xq. The parameters come from sudden short-circuit or standstill frequency response tests, and the fault article gives the negative- and zero-sequence reactances for unbalanced faults.

Excitation Systems

The excitation system supplies and regulates the field current. It sets Ef, and so the terminal voltage and reactive power, and during a nearby fault it can drive the field voltage toward its ceiling to help hold the machine in step. Three families are in use:

  • DC exciters: older commutator machines on the generator shaft, whose output feeds the field through slip rings.
  • AC exciters: alternators whose output is rectified, either by stationary rectifiers feeding slip rings or, in brushless exciters, by diodes rotating on the shaft, so that no sliding contact carries field current.
  • Static exciters: thyristor bridges fed from the generator terminals or an auxiliary bus, which respond within tens of milliseconds because no rotating machine lies in the control path.

The automatic voltage regulator compares the terminal voltage with its setpoint and adjusts the exciter. Limiters hold the machine inside its capability curve: an overexcitation limiter guards the field winding, and an underexcitation limiter guards the underexcited boundary. A power system stabilizer adds a damping signal derived from speed, frequency, or power. Hydroelectric Power Electronics describes static and brushless excitation, the limiters, power system stabilizers, and the IEEE Std 421.5 models that represent them in stability studies.

Permanent-Magnet Synchronous Machines

Permanent magnets in place of the field winding remove the field copper loss, the slip rings, and the exciter, raising efficiency and torque density. They also remove the field current as a control. The magnets fix the rotor flux, so Ef is proportional to speed alone, and a permanent-magnet machine connected directly to a fixed-voltage network cannot adjust its reactive power. Most permanent-magnet machines run from an inverter, which sets the magnitude and phase of the current relative to the rotor and so takes over the role of the field regulator.

Rotor construction changes the reactances. Magnet material has a relative permeability close to that of air, so surface-mounted magnets act as a long air gap: the synchronous reactance is low and nearly equal on the two axes. Magnets buried in the rotor steel leave a low-reluctance steel path along the q-axis, so Xq exceeds Xd, the reverse of a wound-field salient-pole machine. Such interior-magnet machines develop reluctance torque when the drive injects negative d-axis current, which also weakens the field at high speed. BLDC and PMSM Drives covers the control of these machines, and Wind Power Electronics describes permanent-magnet generators behind full-scale converters in wind turbines.

Summary

A synchronous machine turns at ns = 120f/P, where P is the number of poles, locked to the rotating field of its armature. Its field current sets an internal voltage of 4.44fNkwΦ per phase behind the synchronous reactance Xs = Xl + Xa, which open-circuit and short-circuit tests measure.

Real power follows the power angle as 3VtEf sin δ / Xs, with Ef leading for a generator and lagging for a motor, up to a steady-state stability limit at 90° for a round rotor and below 90° for a salient-pole machine. Reactive power follows the excitation, and the capability curve bounds operation by armature heating, field heating, underexcited stability and end-region heating, and the prime mover. Synchronous motors need a starting method but can correct power factor. Transient reactances, excitation systems, and permanent magnets extend the same model to faults, control, and drives.

Related Topics